4.2 Set-point processing
The set-point processing structure is shown in the following picture:
Set-point gradient / ramp
To prevent setpoint step changes, a maximum rate of change is adjustable for pa
-
rameter r setpoint r r.SP. This gradient acts both in positive and negative di
-
rection.
With parameter r.SP set to OFFas in the factory setting, the gradient is switched
off and setpoint changes are made directly.
Configuration level
Set-point processing 42 KS 90-1p / KS 92-1p
0
1
Ü
Xeff
SP.2
SP.E
Internal set-point
Programmer
*
Ö
SP.Hi
SP.Lo
r.SP
-LED
external
set-point
Limiting
Ramp
2nd
set-point
Effektive
set-point
Ü
+
+
8
9
1200
1199
°C
°F
SP.2
SP.E
para
func
Ada
Err
The ramp starts at process value with the following switchings:
- int / ext-setpoint switching
- / switching
- Manual-/ Automatic switching
- at power on
SP SP.2
Index:
Ü
*
Ö
: int/ext-setpoint switching
: configuration
: / switching
SP.Fn
SP SP.2