8 Special functions
8.1 KS90-1 as Modbus master
a
This function is only selectable with BlueControl (engineering tool)!
The KS90-1 can be used as Modbus master ( ConF / othr / MASt =1).The
Modbus master sends its data to all slaves (Broadcast message, controller adress
0). It transmits its data (modbus adress AdrU) cyclic with the cycle time Cycl to
the bus. The slave controller receives the data transmitted by the masters and al-
locates it to the modbus target adress AdrO. If more than one data should be
transmitted by the master controller ( Numb > 1) , the modbus adress AdrU in-
dicates the start adress of the data that should be transmitted and AdrO indicates
the first target adress where the received data should be stored. The following
data will be stored at the logically following modbus target adresses.
With this it is possible e.g. to specify the process value of the master controller as
set-point for the slave controllers.
Special functions
KS 90-1p / KS 92-1p 69 KS90-1 as Modbus master
q
Additions othr (only visible with BlueControl!)
Name Value range Description Default
MASt
Controller is used as Modbus master
0
0
Slave
1
Master
Cycl
0...200
Cycle time [ms] for the Modbus master to transmit its data to the bus.
60
AdrO
1...65535
Target address to which the with AdrU specified data is given
out on the bus.
1
AdrU
1...65535
Modbus address of the data that Modbus master gives to the bus.
1
Numb
0...100
Number of data that should be transmitted by the Modbus master.
0
Master
KS 90-1
programmer
Slaves
KS 90-1, KS 50-1, KS 40-1
KS 40-1 universal
123OK
SP.x
run
Err
Ada
126
125
KS 40-1 universal
123OK
SP.x
run
Err
Ada
126
125
KS 40-1 universal
123OK
SP.x
run
Err
Ada
126
125
KS 40-1 universal
123OK
SP.x
run
Err
Ada
126
125
KS 40-1 universal
123OK
SP.x
run
Err
Ada
126
125
1234
F
°C
°F
SP.2
SP.E
para
func
Ada
Err
1200
1199
KS 90-1 programmer
run
- PrgEdit -
/
02/12:30
Example for transfering the programmer set-point
Vista de pagina 68
1 2 ... 64 65 66 67 68 69 70 71 72 73 74 ... 83 84

Comentarios a estos manuales

Sin comentarios