6 Calibration level
Measured value correction ( CAL) is only visible if ConF / InP.1 / Corr = 1
or 2 is chosen.
The measured value can be matched in the calibration menu ( CAL). Two meth
-
ods are available:
Offset correction
( ConF/ InP.1 / Corr =1 ):
w
possible on-line at the
process
2-point correction
( ConF/ InP.1 / Corr = 2 ):
w is possible off-line with
process value simulator
Calibration level
56 KS 90-1p / KS 92-1p
X
standard setting
offset correction
InL.1
OuL.1
new
display
OuL.1old
X
standard setting
2-point correction
InL.1
InH.1
OuL.1
new
OuH.1
new
display
OuH.1
old
OuL.1old