KS 800 CAN-Interface
Column "as from firmware": C = This datum exists already from operating version 1, however, it was
subject to change (extension) in the course of development.
N = This datum was added as from the specified operating version.
Index
(hex)
Object
(symbolic
name)
Name Type Attri-
bute
as
from
firm-
ware
FB unit
Process data fct.no.0
2001 VAR Status 1Unit-State1 Unsigned8 ro 1.0
2002 VAR Basic hardware options HWbas Unsigned16 ro 1.0
2003 VAR SW options SWopt Unsigned16 ro 1.0
2004 VAR SW code no. SWCode Unsigned16 ro 1.0
2005 VAR SW version SWVersion Unsigned16 ro 1.0
2006 VAR Operating version OPVers Unsigned16 ro 1.0
2007 VAR EEPROM version EEPVers Unsigned16 ro 1.0
2008 VAR Configuration mode selection OPMod Unsigned8 rw 1.0
2009 VAR Self-tuning stop/start of all group controllers
OStartg
Unsigned8 rw 1.0
200A VAR Local data change flag reset Unsigned8 rw 1.0
Parameter and configuration data fct. no. 0
200B VAR Baudrate COM 1 C900 Unsigned16 rw
*
1.0
200C VAR Controller address Adr1 Unsigned16 rw
*
1.0
200D VAR Mains frequency 50/60 Unsigned8 rw
*
1.0C
200E VAR Baudrate COM 2 C900 (CAN baudrate) Unsigned16 rw
*
1.0
200F VAR Controller address Adr2 (CAN Node ID) Unsigned16 rw
*
1.0
2010 VAR Releasing the cooling function for Water Co-
oling
FixedPoint1 rw
*
2.0
2011 VAR Heating-current reset / quicktest Unsigned8 rw 4.0
Process data Fct. no. 2
2020 VAR Status alarm outputs State_alarm_out Unsigned8 ro 1.0
2021 VAR Status dig. inputs/outputs State_dio Unsigned8 ro 1.0
Parameter and configuration data fct.no. 2
2022 VAR Main config. C500 Unsigned16 rw
*
1.0
2023 VAR Main config. C530 Unsigned16 rw
*
1.0
2024 VAR Allocation HC/leakage current C151 Unsigned16 rw
*
1.0C
2025 VAR Heating current cycle Hccycl Unsigned16 rw
*
1.0
2026 VAR Span end for HC input HC 100 FixedPoint1 rw
*
1.0
26 9499 040 49511